Pump connected after boiler thermostat ?

QUESTION:

I recently moved into a house and I've successfully upgraded the CH/HW controls to an 'S-Plan' type system (see previous posts). My modifications only required me to replace a mechanical timeswitch with a programmer, thermostats and 2-port zone valves. In other words, I pretty much ignored what was in the external boiler housing and replaced the single mech timer with some more elaborate switching gubbins.
Over the weekend, I noticed something that I think is a bit odd. The external boiler housing contains the oil-fired boiler (warmflow, no pump overrun required) and a circulating pump on the feed. However, the pump seems to be wired _after_ the boiler thermostat (a small gray box with a knob from 1..5 that supplies mains power to the burnber unit). It strikes me that this is odd and potentially damaging. Surely the circulating pump should be circulating water when either the CH or HW zones require heat, not just when the boiler is in the part of its cycle that fires the burner.
Does what I've described sound normal? Or should I rewire the circulating pump?

ANSWER:

The pump should be running whenever the *external* controls are telling the boiler to fire - even when it's own internal thermostat is telling it not to.
It you wire it up according to the S-Plan diagram in http://content.honeywell.com/uk/homes/systems.htm it will be fine!
In brief, the timer and room stat control the CH zone valve. The timer and cylinder stat control the HW zone valve. Whenever either or both zone valves are open, power is supplied to the boiler and pump, in *parallel*.


Submit your comment or answer




Privacy Policy