QUESTION:

I just bought a new buderus delta boiler U012-24K and got installed. I did not have the chance to read the instructions that came with the boiler itself before I received the boiler nor the specific requirements were mentioned in the info sheets made for advertisment purpose. As I read the instructions more carefully, I found out that in a flat like mine where the heating is done through the heating elements under the floor -I mean between the two levels- one should set a lower temperature. On another page in the instructions it says that long term usage on low temperatures causes condensation which may eventually lead to corrosion of the exhaust pipes. To prevent that it says that one should get installed a three-way cock which was not installed at all.
As I applied to my firm which sold the boiler and made the installation, they said that it is not necessary though could not say in which situation it would be necessary to install a three-way cock.
Do you have any information about that situation? Are the instructions wrong? Which is correct?

ANSWER:

Yes, the instructions are correct. The boiler can be run with a return water temp as low as 117 degrees F. so long as the correct controls are applied. Buderus makes a logic controller for your boiler to allow boiler to function for your application without the 3 way mixing valve. This controller is not cheap. It will help reduce fuel consumption (it integrates outdoor reset into the boiler function) and will protect your boiler. Contact your installers for this control. If they resist, contact Buderus and they can suggest a competent installer in your area to straighten out your system.